A wall clad two years ago starts sounding hollow when you tap it. A corner lifts. Hairline cracks appear along a joint that looked perfect at handover. Nobody agrees on whose fault it is: the contractor blames the material, the supplier blames the substrate, the substrate was never tested by anyone.

This is a working diagnostic note for that argument. It covers the six failure modes we actually get called about, what each one looks like up close, and how to tell an installation error from a genuine manufacturing defect before you spend money on a repair that will not hold.

Read the pattern before you blame the material

One cracked sheet is an event. Twenty cracked sheets in the same band of the elevation is a cause. Before anything else, walk the wall and record where failures sit:

  • Scattered, no pattern — usually handling damage or isolated bonding misses.
  • Concentrated on one orientation — the sun-facing side, or the side that takes driven rain. Thermal or water load.
  • Concentrated at slab level, floor by floor — structural movement joints that were bridged over instead of carried through.
  • Concentrated at the top of the wall or under copings — water getting in behind and running down.
  • Everything, everywhere, evenly — genuinely suspect the batch, the adhesive, or the substrate preparation.

Photograph it on a grid before anyone touches it. Half of these arguments are settled by a photo taken before the repair crew arrived, and almost nobody takes one.

Hollow spots: the sound that means the bond failed

Tap the surface with a coin or a rubber mallet. Bonded areas give a dull thud. Debonded ones ring. Mark the ringers with chalk and count them as a percentage of the panel area — that number decides the repair.

Hollowness comes from three places, and they look different:

  • Dry spots in the adhesive bed. The trowel pattern closed over without full transfer. You will find a smooth adhesive face on the back of the sheet and a matching smooth patch on the wall, both with no fracture. Under 0.5 m², cut out and re-bond. Spread across the elevation, it is a workmanship problem, not a material one.
  • Substrate that was never strong enough. Pull the sheet off and the render surface comes with it, leaving exposed basecoat or board. The bond did not fail — the substrate did. This is the single most common cause we see on retrofit jobs.
  • Water that got behind and froze. Hollow patches that appeared after the first winter, growing outward from joints and penetrations. Ice expansion separates the basecoat from what is underneath, and the cladding goes with it.

Testing the substrate first is cheap and takes a day. See what is worth checking in our substrate preparation notes — a pull-off test on sound render should give you figures well above the dead load of a 3.0–10.5 kg/m² cladding, and if it does not, no adhesive on the market will save the job.

Cracking along the joints

Hairline cracks that run with the joint, not across the sheet, are almost always movement. The sheets are thin — 2–9 mm depending on texture — and they follow whatever the substrate does. If the substrate has a control joint and the cladding does not, the cladding will make one for itself, usually within the first heating season.

Three things produce it:

  • Movement joints bridged over. Cladding run continuously across a structural joint. Cracks appear as a straight vertical line, often floor-height. Needs the joint reinstated through the cladding, not a sealant smear over the crack.
  • Sheets butted tight with no gap. Thermal expansion of the substrate has nowhere to go, so it goes into the joint line. A gap filled with a flexible sealant absorbs it; a tight butt joint does not.
  • Cracks that radiate from a fixing. Mechanical fixings through a thin sheet create a stress point. If you see star cracks around anchors, the fixing detail is wrong for the material, not the material wrong for the wall.

Cracks that wander diagonally across a sheet rather than following a joint are different. Those usually trace back to impact, to a sheet bent past its radius during handling, or to a substrate defect telegraphing through. Checking sheets before they go on the wall catches most of the second kind.

Delamination: when the sheet itself comes apart

This one is genuinely material, and it is rare. MCM flexible stone is a modified clay composite bonded to a reinforcing backing. When the bond between those layers fails, the face lifts as a bubble or peels as a flap, and the backing stays stuck to the wall.

Delamination looks nothing like debonding: the adhesive is still holding, the substrate is sound, and the failure plane is inside the sheet. It is also usually batch-localised — the same production run, the same palette, the same delivery. Photograph the backing, keep the sheet, and record the lot number. That is a claim with a serial number on it, and it is the one failure mode where a replacement order is the right answer.

What is not delamination: a face that lifts where water has been sitting under an unsealed edge for a season. That is water ingress, and replacing the sheets without fixing the edge detail repeats it.

Colour shift and fading

Every exterior material moves in colour. The question is how much and how evenly.

  • Even lightening across the whole elevation — normal UV ageing. Darker pigments carry more load here; a near-black texture in continuous tropical sun will show it faster than a mid-tone.
  • Patchy fading that follows the sheet layout — batch variation. Sheets from different lots installed side by side drift apart over a couple of summers. This is why lot consistency belongs in the acceptance check, and why ordering the full quantity for an elevation in one run matters.
  • Chalking or a powdery surface — surface degradation, and worth a conversation with the supplier.

Our notes on UV, rain and freeze-thaw behaviour cover what is realistic to expect by climate, including the surface temperature range panels reach on insulated walls in full sun.

Efflorescence and staining

White deposits on the surface are salts, and salts need water to travel. Find the water and the stain explains itself. On insulated walls the usual suspects are unsealed joints, an unflashed coping, or a penetration that was never detailed — which is the same water path covered in the ETICS and external insulation notes.

Rust-coloured streaks are different: those come from a metal component, a fixing, a lintel or a bracket that was not corrosion-resistant for an exterior wet zone. Cleaning the streak without replacing the metal buys you one season.

Edge and corner lift

Corners and edges take the sun, the driven rain and the knocks. They also have the least adhesive behind them if the trowel pattern was stopped short. Lift here is usually a detailing gap: no termination profile, no sealant in the movement joint, or an external corner left as a butt joint instead of a returned or profiled edge.

Fix the detail, then the sheet. Doing it the other way round is how the same corner gets repaired twice.

Installation error or manufacturing defect

What you seeMost likely causeFailure planeWho pays
Hollow ring, smooth adhesive face both sidesIncomplete adhesive transferAdhesive / sheet interfaceInstallation
Sheet comes off with render attachedSubstrate below design strengthInside the substrateSubstrate / design
Straight crack at floor level, full heightMovement joint bridged overThrough the sheetDesign / installation
Face bubbles up, backing stays bondedInter-layer bond failureInside the sheetMaterial — claim it
Patchy fade following sheet layoutMixed production lotsSurfaceSpecification / ordering
Hollow patches appearing after winterWater ingress then freezeSubstrate / adhesiveDetailing

Two of those six are the supplier’s problem. Four are not, and the difference is visible in the failure plane if you look before you scrape.

What to send with a claim

Suppliers cannot act on “it’s cracking”. They can act on a pack. Put together:

  • Photos before repair: wide shot showing the pattern, close shot showing the failure plane, one with a scale reference.
  • Lot or batch code from the packaging or the sheet backing.
  • Installation date, exposure orientation, and the substrate the sheets went onto.
  • Adhesive product and trowel size used, if known.
  • Substrate pull-off test results, if you have them. If you do not, this is the moment to get them.
  • The percentage of affected area, not the number of sheets.

A claim without lot numbers and substrate data turns into a two-month email exchange. One with them usually gets resolved in a week.

The other half of prevention is simpler: check the sheets on arrival, test the substrate before the first trowel, and keep movement joints where the building put them. Our installation guide and the adhesive selection notes cover both in more detail than fits here, and the specification sheet has the tolerance figures to check against.

If a failure is not on this page, it is worth a look. Send photographs and the lot code to our technical team and we will tell you which of the six it is, or admit it is a seventh.

Frequently Asked Questions

How do I know if a crack is serious or just cosmetic?

A hairline crack that follows a joint and has not opened wider over a full heating season is usually cosmetic and can be sealed. A crack that is widening, that runs diagonally across a sheet, or that lets water behind is structural to the cladding and needs the cause found first.

Can hollow sheets be re-bonded without replacing them?

Under about 0.5 m² per sheet, yes — inject adhesive through small drilled holes and weight the area until it cures. Beyond that, or where the substrate is the failure plane, replacement is cheaper than doing it twice.

Does a hollow sound always mean the sheet will fall off?

No. A small debonded area with sound edges often stays put for years, because the perimeter bond carries the load. It becomes a real risk when hollow areas connect, when they sit at the top of a sheet, or when water can get in behind and freeze.

How long should MCM flexible stone last on an exterior wall?

That depends far more on the substrate and the detailing than on the sheet. On a sound, properly prepared substrate with movement joints carried through and water kept out of the assembly, service life is measured in decades. On a weak or wet substrate, no thin cladding reaches its design life.

Is delamination covered as a material defect?

If the failure plane is inside the sheet, with the adhesive still holding and the substrate still sound, it is a manufacturing defect and should be claimed against the lot. Document it with photographs before any repair, because the evidence disappears once the sheet comes off.

Why did only the sun-facing side fade?

UV load is not evenly distributed around a building. The orientation that takes the most direct sun ages fastest, and dark pigments absorb more energy than light ones. It is normal for elevations to drift apart in colour over several years.